Single Phase SimplexSXL21=3, SXL24=3, SXH21=3, and SXH24=3Manufactured by SJE-Rhombus®Installation Instructions and Operation/Troubleshooting ManualTh
OperationsThree phase simplex control panels are designed to operate in a three fl oat system as standard. When all fl oats are in the open or OFF posit
FusesCheck the continuity of the fuse. With power OFF, pull the fuse out of the fuse block. With the ohm-meter on the R X 1 scale, measure resistance.
7000 Apple Tree AvenueBergen, New York 14416Phone: 1-800-543-2550Email: [email protected]©SJE-RhombusPrinted in USAPN102504
Installation InstructionsFIGURE 3Clamp detail, mounting to Liberty Pumps “Quick Tree”:Note: Approximate activation level of 1.5 inches (4 cm) above or
Mounting the Control Panel1. Determine mounting location for panel. If dis-tance exceeds the length of either the fl oat switch cables or the pump pow
Simplex control panels are designed to operate in a three fl oat system as standard. When all fl oats are in the open or OFF position, the panel is inac
WARNING: Disconnect incoming power to panel. 1. Isolate the fl oat by disconnecting one or both of the fl oat leads from the fl oat terminals.2. Pla
7000 Apple Tree AvenueBergen, New York 14416Phone: 1-800-543-2550Email: [email protected]*NOTE: Liberty Pumps, Inc. assumes
Three Phase SimplexSX34=3-131, SX34=3-141, SX34=3-171, SX34=3-191, SX34=3-511 and SX54=3-121, Manufactured by SJE-Rhombus®Installation Instructions an
Installation of FloatsStandard three phase simplex panels are designed to operate with three fl oats. These fl oats operate the pump stop, pump start, a
Mounting the Control Panel1. Determine mounting location for panel. If distance exceeds the length of either the fl oat switch cables or the pump powe